GAMATRONIC ELECTRONIC INDUSTRIES LTD.
42
POWER
+
PARALLEL
UPS,
USER GUIDE
,
REL
.
2.0
5. Select Configure, option 5, to configure the Power+ modules:
[Main Menu > SETUP > (password) > Ent > Service]
1> ------ 4> DryOut Test 7> --------
2> UPSs 5> Configure 8> Powr.Calib
3> ------- 6> En/Dis shar 9> SC2012..
Select, then Enter
Figure 41: Service menu
6. Select # UPSs (total), option 2, to specify the total number of modules in the system:
[Main Menu > SETUP > (password) > Ent > Service > Configure]
1> # OF UPSs (redundancy) 5> Dry, Alarms
2> # OF UPSs (total) 6> Calibration
3> # OF BATT 7> Parallel/StandAlone
4> Static Switch Setup 8> REM COMMAND
Figure 42: Configure menu
7. Use the arrow keys to specify the total number of modules installed in the Power+, and then press
Ent:
[Main Menu > SETUP > (password) > Ent > Service > Configure > # OF UPSs (total)]
Set number of UPSs (total)
04 (02 redundant)
Figure 43: # of UPSs (Total)
8. Select 1, # of UPSs (Redundancy) in Figure 42 to specify the number of modules used for
redundancy:
[Main Menu > SETUP > (password) > Ent > Service > Configure > # OF UPSs (redundancy)]
Set number of UPSs (Redundancy)
01 (04 total)
Figure 44: # of UPSs (Redundancy)
Note: The redundant modules are designated to replace other system modules when they stop working.
For example, a 100-kVA system with 10 modules of which two are configured for redundancy can
deliver a maximum of 80 kVA.