GAMATRONIC ELECTRONIC INDUSTRIES LTD.
116
POWER
+
PARALLEL
UPS,
USER GUIDE
,
REL
.
2.0
5. Press Ent to continue:
[Main Menu > SETUP > (password) > Ent > Service > Configure > Calibration > DC-I Calibration]
1> Calibrate Battery #1 Current
Figure 238: Calibrating DC current
6. Using the arrow keys, set the actual current and then press Ent:
[Main Menu > SETUP > (password) > Ent > Service > Configure > Calibration > DC-I Calibration >
Ent]
CURRENT METER #01 CALIBRATION
Enter the value of the actual current:
02000 (X0.1)A
Figure 239: Entering actual current
7.12.3.7 Selecting Standalone or Parallel Operation
1. Select Parallel/StandAlone:
[Main Menu > SETUP > (password) > Ent > Service > Configure]
1> # OF UPSs (redundancy) 5> Dry, Alarms
2> # OF UPSs (total) 6> Calibration
3> # OF BATT 7> Parallel/StandAlone
4> Static Switch Setup 8> REM COMMAND
Figure 240: Service > Configure menu
2. Select Stand Alone or Parallel by using the ▲▼arrow keys and Ent:
[Main Menu > SETUP > (password) > Ent > Service > Configure > Parallel/StandAlone]
--- Parallel / Stand-Alone Setup ---
SELECT - 1: Stand Alone (selected)
SELECT - 2: Parallel
Figure 241: Setting standalone or parallel operation