7.12.3.8 Enabling/Disabling Remote Commands
1. Select REM COMMAND:
[Main Menu > SETUP > (password) > Ent > Service > Configure]
1> # OF UPSs (redundancy) 5> Dry, Alarms
2> # OF UPSs (total) 6> Calibration
3> # OF BATT 7> Parallel/StandAlone
4> Static Switch Setup 8> REM COMMAND
Figure 242: Service > Configure menu
2. Enable or disable remote commands by using the ▲▼arrow keys and Ent:
[Main Menu > SETUP > (password) > Ent > Service > Configure > REM COMMAND]
--- REMOTE COMMANDS EN / DIS ---
SELECT - 1: Disable (selected)
SELECT - 2: Enable
Figure 243: Enabling/disabling remote commands
7.12.4 Enabling/Disabling Current Sharing
1. Select En/Dis shar:
[Main Menu > SETUP > (password) > Ent > Service]
1> ------ 4> DryOut Test 7> --------
2> UPSs 5> Configure 8> Powr.Calib
3> ------- 6> En/Dis shar 9> SC2012..
Select, then Enter
Figure 244: Service menu
2. Enable or disable current sharing by using the ▲▼arrow keys and Ent::
[Main Menu > SETUP > (password) > Ent > Service > Configure > En/Dis shar]
SELECT 1: RST CURRSHAR DISBLD:(selected)
SELECT 2: RST CURRSHAR ENBLD:
--- CURRENT SHARIN RESET EN / DIS ---
Figure 245: Enabling/disabling current sharing