4. To turn on the storage system, click Power Management > Power on
Storage System. At the confirmation message, click Submit.
5. To turn off the storage system, click Power Management > Power off
Storage System. At the confirmation message, click Submit.
Using LEDs to diagnose problems
The storage system LEDs provide system status and diagnostic indicators.
If the storage system used in a remote TrueCopy configuration restarts with
the TrueCopy status of enabled, the following occur:
• The path used by TrueCopy becomes blocked. Notifications from the
Hitachi Device Manager - Storage Navigator email alert function, SNMP
Agent Support function, and SNMP trap occur when the path is blocked.
Follow the instructions in the notification. The blocked path recovers
automatically after restarting the storage system.
• If the TrueCopy pair status is PAIR or COPY, the pair changes to PSUE. In
this case, suspend the pairs before restarting the storage system.
Power LED does not go on
Procedure
1. Set the main switch to on.
2. Is the Power LED on at the controller?
• Yes: Go to step 9.
• No: Power on the host computer.
3. Is the Power LED on at the controller?
• Yes: Go to step 9.
• No: Set the main switch to off.
4. Check that the PDU on the rack is delivering power to the storage
system.
5. Verify that the AC cable is correctly connected to the plug socket and the
equipment.
6. Set the main switch to on.
7. Is the Power LED on at the controller?
• Yes: Go to step 9.
• No: Set the main switch to off.
8. Contact your administrator. Go to step 10.
9. Is the Ready LED on?
• Yes: Continue to use the equipment, even if the green Ready LED
blinks fast.
• No: Use the following corrective action. See
Ready LED does not go on
or Ready LED went on and then off on page 390.
Troubleshooting the storage system 389
Service Guide for VSP Gx00 and VSP Fx00 Models