4. Series 8 IOTA Pinouts
4.2. Differential Analog input IOTA (Models 8X-TAIDA1 and 8X-TAIDB1)
64 Series 8 I/O User's Guide R500
Honeywell April 2017
Custom wiring scenarios
Note: You must plan cautiously when you cut the JP1 to JP16 jumpers as they are
non-repairable. That is, once these jumpers are cut, you cannot short these jumpers.
Slidewire: Series 8 does not support Slidewire.
Jumper configuration for differential configuration
Jumper configuration for the non-redundant differential Analog Input channel is
illustrated in the following figure. Each channel is associated with 250Ω range spool or
dropping resistor for sources that deliver 4-20mA. In addition, one jumper and three
jumper pins are provided for each channel.
For example, channel 1 consists of JP1, J248, J249, and J250.