4. Series 8 IOTA Pinouts
4.2. Differential Analog input IOTA (Models 8X-TAIDA1 and 8X-TAIDB1)
R500 Series 8 I/O User's Guide 63
April 2017 Honeywell
by cutting the jumper (for example, JP1). Configure the jumper settings as single-
ended according to the Table 15 Series 8 differential Analog Input 9 inch and 12 inch
IOTAs – terminal block 2.
Note: You must plan cautiously when you cut the JP1 to JP16 jumpers as they are
non-repairable. That is, once these jumpers are cut, you cannot short these jumpers.
Voltage input (Device ground)
Voltage output transducer is connected across TB1-2 and TB2-16 as illustrated in the
following figure. To use voltage output transducer, disconnect the 250Ω spool resistor
by cutting the jumper (for example, JP1). Configure the jumper settings for differential
configuration according to the Table 15 Series 8 differential Analog Input 9 inch and 12
inch IOTAs – terminal block 2.