Paramete
r
Description Conguration
Principle
Default Value
Network Networking mode for
the teamwork. The
networking mode set
on the screen must be
consistent with the
actual networking
mode. Otherwise, the
teamwork control
function will be
unavailable. If the
networking mode
changes, select the
corresponding
networking mode on
the screen. If the
networking mode is
changed on the
screen, the software
will restart and then
run in the new
networking mode.
Networked over CAN
or MAC_CAN. CAN
indicates teamwork
control over a CAN
bus, MAC_CAN
teamwork control
over an FE port.
MAC_CAN
Total
number of
units
Number of the smart
cooling products in
this group (1 to 32
can be set).
Total number of the
smart cooling
products in this group.
3
Number
of running
units
Number of active
units in a group. The
value ranges from 1
to Total number of
units.
The master unit
assigns the devices to
be active units by the
device number,
beginning with the
address 1 until to
Number of running
units. The rest will
become the standby
ones.
2
Rotation Disable or enable the
active and standby
smart cooling
products to change
identity after a certain
time, maximizing their
service life.
This function is
recommended when
the heat is even.
Disable
Rotation
period
Rotation days (1–30). 7 by default. 7 day(s)
Rotation
time
24 hours in a day (0–
23).
0 by default. 0
NetCol5000-A025 In-row Air Cooled Smart Cooling
Product
User Manual (300 mm Width) 4 Power-On Commissioning
Issue 15 (2020-12-10) Copyright © Huawei Technologies Co., Ltd. 115