Paramete
r
Description Conguration
Principle
Default Value
Teamwork
function
Disable or enable the
teamwork function. If
the teamwork
function is disabled,
this device is
operating according
to its own control. If
the teamwork
function is enabled,
this device works in
harmony with others
that in the same
group.
Set this parameter
based on the onsite
device heat
distribution.
Disable
Teamwork
mode
Set the teamwork
mode. The options
include Smart and
iCooling.
Determine whether to
enable the iCooling
mode based on onsite
heat load variations.
If the heat load varies
greatly, it is
recommended that
you enable the
iCooling mode. The
parameter can only
be
modied on the
ECC WebUI and
cannot be modied
on the smart cooling
product screen.
Smart
Enable
L1/L2
linkage
Enable or disable
L1/L2 linkage.
Set this parameter
based on site
requirements. The
parameter can only
be modied on the
ECC WebUI and
cannot be
modied
on the smart cooling
product screen.
Disable
NetCol5000-A025 In-row Air Cooled Smart Cooling
Product
User Manual (300 mm Width) 4 Power-On Commissioning
Issue 15 (2020-12-10) Copyright © Huawei Technologies Co., Ltd. 114