Menu Parameter Description Default Value
Heating
mode
If Dehumidifying
heating is selected, the
electric heater starts
heating based on the
current temperature
only after the
dehumidication
function is enabled. If
Low-temp heating is
selected, the electric
heater starts heating
based only on the
current temperature, no
matter the
dehumidication
function is enabled or
not. If Dehumid & low-
temp heat is selected,
the electric heater starts
heating when the
dehumidication and
heating condition or the
low temperature heating
condition is met.
Dehumidifying
heating
Humidifying
function
Enable indicates that
the electric humidier
will be started when the
ambient humidity is
lower than the certain
humidity range of the
humidity set point.
Disable indicates that
the electric
humidier
will not be started.
Enabled when active
power indicates that the
electric
humidier will
be started when the
main power is active
and the ambient
humidity is lower than
the certain humidity
range of the humidity
set point.
Enable