Paramete
r
Description Conguration
Principle
Default Value
Networkin
g mode
Networking mode
for the teamwork.
The networking
mode set on the
screen must be
consistent with the
actual networking
mode. Otherwise,
the teamwork
control function will
be unavailable. If the
networking mode
changes, select the
corresponding
networking mode on
the screen. If the
networking mode is
changed on the
screen, the software
will restart and then
run in the new
networking mode.
Networked over
CAN or MAC_CAN.
CAN network
indicates teamwork
control over a CAN
bus, MAC_CAN
network teamwork
control over an FE
port.
CAN network
Number
of smart
cooling
products
in this
group
Number of the
smart cooling
products in this
group (1 to 32 can
be set).
Total number of the
smart cooling
products in this
group.
3
Number
of running
smart
cooling
products
in this
group
Number of active
units in a group. The
value ranges from 1
to Number of smart
cooling products in
this group.
The host allocates
running units by
smart cooling
product unit address
in ascending order,
which is from 1 to
32. The rest will
become the standby
ones.
2
Rotation
function
Disable or enable
the active and
standby smart
cooling products to
change identity after
a certain time,
maximizing their
service life.
This function is
recommended when
the heat is even.
Disable
Rotation
period
Rotation days (1–
30).
7 by default 7 day (s)
NetCol5000-A025 In-row Air Cooled Smart Cooling
Product
User Manual (300 mm Width) 4 Power-On Commissioning
Issue 15 (2020-12-10) Copyright © Huawei Technologies Co., Ltd. 140