Step 2 Set teamwork control parameters.
All teamwork control parameters can be set on the master smart cooling product.
Only Teamwork group No., smart cooling product address, Enable teamwork
CAN resistor, Teamwork function and Networking mode can be set on slave
smart cooling products. Other parameters of the slave units will be
modied by
the master unit synchronously. Table 4-15 describes how to set the parameters.
Table 4-15 Teamwork settings
Paramete
r
Description Conguration
Principle
Default Value
Teamwork
group No.
The number of the
teamwork controlled
group, which is the
same for all the
devices in the group.
Set the assigned
teamwork control
number.
1
Smart
cooling
product
address
Smart cooling
product addresses
should be dierent
from each other.
Set the assigned unit
address.
NA
Enable
Teamwork
CAN
resistor
Indicates the build-
out resistor status of
each smart cooling
product in a
teamwork group. Set
the parameter if
CAN network is
used.
Set this
parameter to No
for non-
teamwork
scenarios.
For teamwork
scenarios, set this
parameter to Yes
for the
rst and
last smart cooling
products in a
teamwork group,
and set it to No
for other smart
cooling products.
No
Teamwork
function
Disable or enable
the teamwork
function. If the
teamwork function
is disabled, this
device is operating
according to its own
control. If the
teamwork function
is enabled, this
device works in
harmony with others
that in the same
group.
Set this parameter
based on the onsite
device heat
distribution.
Disable