Paramete
r
Description Conguration
Principle
Default Value
Requirem
ent
control
Enable or disable the
requirement control
for the master
device.
When the
requirement
control is Disable,
the master device
does not
synchronize data
to the slave
device, and all the
smart cooling
products operate
based on their
own
requirements, not
referring to the
mode delivered
by the master
device.
When the
requirement
control is Anti-
competitive
running, the
master device
synchronizes data
(the temperature
and humidity
control type and
set points of the
master device
and other
parameters) to
the slave device,
and all the smart
cooling products
in the group refer
to the mode
delivered by the
master device.
When the
requirement
control is Indoor
fan
unied
control or
Central load
Anti-competitive
running is
recommended for
the following
scenario: In one
teamwork, the
temperature and
humidity control
type and
temperature and
humidity set point
of units are the
same, and device
heat loads are
distributed evenly.
Disable
NetCol5000-A025 In-row Air Cooled Smart Cooling
Product
User Manual (300 mm Width) 4 Power-On Commissioning
Issue 15 (2020-12-10) Copyright © Huawei Technologies Co., Ltd. 142