Paramete
r
Description Conguration
Principle
Default Value
distribution, all
smart cooling
product fans in
the group rotate
at the same
speed.
Cascade
function
After the
requirement control
is enabled, you can
congure Cascade
function. The
cascade function
starts standby smart
cooling products if
the active one
cannot meet the
refrigerating
requirements.
If the heat load to
the device increases,
the cascade function
is recommended.
Disable
Cold aisle
temperatu
re and
humidity
sharing
When this parameter
is enabled, the smart
cooling product,
which is not
congured with the
cold aisle T/H sensor
in the group, is
logically controlled
by using the
acquired value of the
congured cold aisle
T/H sensor.
This parameter can
be enabled when
there are at least
two smart cooling
products in the
group are
congured with cold
aisle T/H sensors.
Disable
Hot aisle
temperatu
re and
humidity
sharing
When this parameter
is enabled, the smart
cooling product,
which is not
congured with the
hot aisle T/H sensor
in the group, is
logically controlled
by using the
acquired value of the
congured hot aisle
T/H sensor.
This parameter can
be enabled when
there are at least
two smart cooling
products in the
group are
congured with hot
aisle T/H sensors.
Disable
Step 3 Complete the teamwork settings for all the smart cooling products by performing
Step 1 and Step 2.
NetCol5000-A025 In-row Air Cooled Smart Cooling
Product
User Manual (300 mm Width) 4 Power-On Commissioning
Issue 15 (2020-12-10) Copyright © Huawei Technologies Co., Ltd. 143