Item Method Troubleshooting
After the electrode
humidier starts, choose
Running > Device Details
> Humidier on the main
screen to make sure that
the current of each phase
is not less than 2.0 A
(conductivity > 100).
Replace the electrode humidier
cylinder.
Wet lm
humidier
The humidier oat has
no scale, and humidier
oat functions properly.
Clean or replace the humidier
oat.
The wet lm and
humidier water pan are
clean and have no scale.
Replace the wet lm humidier.
The wet lm should be replaced
every 12 months.
No operating overtime
alarm is generated on the
wet lm humidier.
Replace the wet lm humidier.
The upstream water pan
lter of the humidier
pump is not dirty or
blocked.
Remove and clean the water pan
lter.
Remove the two screws and sheet metal fastener from the water pan lter and
pull out the
lter, as shown in Figure 6-3.
Figure 6-3 Cleaning the water pan lter