Context
The water pump is located under the wet lm humidier.
Procedure
Step 1 Tap Shutdown on the LCD home screen to turn o the smart cooling product
switch in the PDC.
NO TICE
Exercise caution because the device is still energized after it is shut down on
the LCD.
Before removing the water pump, block the water inlet pipe of the pump to
prevent water
overowing out of the water pan and water pipe.
Step 2 Open the rear door and remove the air lter.
Step 3 Cut o the ties on the water inlet pipe for the wet lm humidier.
Figure 6-35 Cutting cable ties
Step 4 Hold the release sleeve by hand and remove the water inlet pipe.
NetCol5000-A025 In-row Air Cooled Smart Cooling
Product
User Manual (300 mm Width) 6 System Operation and Maintenance
Issue 15 (2020-12-10) Copyright © Huawei Technologies Co., Ltd. 262