Item Specications
Water inlet pipe to
the humidier
G 1/2 inch inner screw thread
Installation Requirements
NO TICE
When the total load power of servers corresponding to a single smart cooling
product is less than 5 kW or the equipment room airtightness is not satisfactory,
the indoor humidity might be relatively high, which is not a product quality issue.
You are advised to install a
dehumidier in the equipment room in this case.
Table 2-6 Installation requirements
Item Specications
Equipment room door Width ≥ 0.9 m; height ≥ 2.3 m
Floor
Bearing capacity ≥ 350 kg/m
2
; height of the raised oor
≥ 250 mm
Installation mode Installed on a concrete oor, a base, or an ESD oor
Pipe and cable
routing
Cables and pipes can be routed from the top or bottom
Equivalent length of
one-way pipe
≤ 80 m
Height dierence
between the indoor
and outdoor units
If the outdoor unit is placed higher than the indoor
unit, the maximum vertical distance between them
is 20 m.
If the indoor unit is placed higher than the outdoor
unit, the maximum vertical distance between them
is 5 m.
Thickness of the
thermal insulation
foam
≥ 13 mm
Inner diameter of the
thermal insulation
foam
Liquid pipe: 16 mm
Gas pipe: 19 mm
Drainage Drainpipes can withstand a high temperature greater
than or equal to 85°C (for the smart cooling products
congured with electrode humidiers)
NetCol5000-A025 In-row Air Cooled Smart Cooling
Product
User Manual (300 mm Width) 2 Product Description
Issue 15 (2020-12-10) Copyright © Huawei Technologies Co., Ltd. 23