Item Specications
Outdoor temperature Working with the NetCol500–A032 (including low–
temperature components): –40°C to +45°C
Working with the NetCol500–A036 (including low–
temperature components): –40°C to +55°C
Working with the NetCol500–A036: –20°C to +55°C
Working with the NetCol500-A026SC11E0: –20°C to
+45°C
Working with the NetCol500-A0265S11E0: –20°C to
+55°C
Working with the NetCol500-A0265S11E0 (including
low–temperature components): –40°C to +45°C
Protection level Indoor unit: IP20
Outdoor unit: IPX5
Altitude 0–1000 m. When the altitude is greater than 1000
meters, the cooling capacity is derated. The maximum
operating altitude is 4000 meters. For the detailed
derated data, reference the Table 2-4.
Table 2-4 Altitude table
Height
0 1000 1500 2000 2500 3000 3500 4000
Density correction 1 0.88
7
0.83
5
0.78
5
0.73
7
0.69
2
0.64
9
0.60
8
Air volume
correction
1 0.88
7
0.83
5
0.78
5
0.73
7
0.69
2
0.64
9
0.60
8
Refrigeration
volume correction
1 0.94
0
0.90
9
0.87
8
0.84
6
0.81
5
0.78
4
0.75
3
Physical Ports
Table 2-5 Physical ports
Item
Specications
Refrigerant liquid pipe Copper pipe, with an outer diameter of 5/8 inch (15.88
mm) and thickness of 1.0 mm, withstanding a pressure
not smaller than 4.5 MPa, welding
Refrigerant gas pipe Copper pipe, with an outer diameter of 3/4 inch (19.05
mm) and thickness of 1.0 mm, withstanding a pressure
not smaller than 4.5 MPa, welding