M7i Router Environmental Specifications
Table 44 on page 78 specifies the environmental conditions required for normal router
operation. In addition, the site should be as dust-free as possible. Dust can clog air intake
vents and filters, reducing cooling system efficiency. Check the filters and vents frequently,
cleaning them as necessary. For more information, see “Routine Maintenance Procedures
for the M7i Router” on page 189.
Table 44: Router Environmental Tolerances
ToleranceDescription
No performance degradation to 10,000 ft (3048 m)Altitude
Normal operation ensured in relative humidity range of 5% to 90%,
noncondensing
Relative humidity
Normal operation ensured in temperature range of 32°F to 104°F
(0°C to 40°C)
Temperature
Tested to meet Telcordia Technologies Zone 4 earthquake
requirements
Seismic
•
AC: 1400 BTU
•
DC: 1600 BTU
Thermal output
NOTE: Install the router only in restricted or service areas, such as dedicated
equipment rooms and equipment closets, in accordance with Articles 110-16,
110-17, and 110-18 of the National Electrical Code, ANSI/NFPA 70.
For additional safety guidelines and requirements, see “General Safety
Guidelines for Juniper Networks Devices” on page 225.
Related
Documentation
M7i Router Physical Specifications on page 74•
• M7i Router Power Requirements on page 79
• M7i Router Description on page 3
M7i Chassis Grounding, Connection, and Cable Specifications
To ground a router, connect a grounding cable to earth ground and then attach it to the
chassis grounding point on the rear of the chassis.
Table 45 on page 79 summarizes the specifications for the groundingcable, which you
must supply.
Copyright © 2019, Juniper Networks, Inc.78
M7i Multiservice Edge Router Hardware Guide