3. Rotate the anti-tilt wire bails outward until they engage with the hooks in the socket.
4.
Fully tighten the Torx T30 nuts in the installation sequence shown on the cold plate
assembly. Tighten the screws until they stop; then, visually inspect to make sure that there is
no gap between the screw shoulder beneath the cold plate assembly and the processor
socket. (For reference, the torque required for the fasteners to fully tighten is 0.9-1.3 newton-
meters, 8-12 inch-pounds.)
Step 5. Remove the module handle from the NeptCore module.
Figure 162. Removing the module handle
a. Rotate the screws as illustrated above to unlock the handle.
b.
Separate the handle from NeptCore module.
Notes: A new NeptCore module comes with a handle.
1. To replace an old NeptCore module with a new one, remove the handle of the new one as
illustrated above.
2. To replace processors without changing the NeptCore module, a handle is not needed. Skip
Step 5 on page 165 and proceed with further installation.
Step 6. Install the cold plate covers. Press the cover down as illustrated below.
Chapter 5. Hardware replacement procedures 165