Address Name Default seng Category Data type Factor A M
0x2C00
(P300.00)
Motor control mode V/f characterisc control
(VF
C open loop) [6]
general U8 1 PC -
0x2C01:001 Motor parameters: Number of pole pairs - (Read only) MCTRL U8 1 - -
0x2C01:002 Motor parameters: Stator resistance 10.1565 Ω * MCTRL U32 10000 P -
0x2C01:003 Motor parameters: Stator leakage inductance 23.566 mH * MCTRL U32 1000 P -
0x2C01:004
(P320.04)
Motor parameters: Rated speed Device for 50-Hz mains:
1450 rpm Device for 60-
Hz mains: 1750 rpm
MCTRL U16 1 P -
0x2C01:005
(P320.05)
Motor parameters: Rated frequency Device for 50-Hz mains:
50.0 Hz Device for 60-Hz
mains: 60.0 Hz
MCTRL U16 10 P -
0x2C01:006
(P320.06)
Motor parameters: Rated power 0.25 kW * MCTRL U16 100 P -
0x2C01:007
(P320.07)
Motor parameters: Rated voltage 230 V * MCTRL U16 1 P -
0x2C01:008
(P320.08)
Motor parameters: Cosine phi 0.80 MCTRL U16 100 P -
0x2C01:010 Motor parameters: Motor name MCTRL STRING[25] 1 P -
0x2C02:001
(P351.01)
Motor parameter (ASM): Rotor resistance 8.8944 Ω * MCTRL U32 10000 P -
0x2C02:002
(P351.02)
Motor parameter (ASM): Mutual inductance 381.9 mH * MCTRL U32 10 P -
0x2C02:003
(P351.03)
Motor parameter (ASM): Magnesing current 0.96 A * MCTRL U16 100 P -
0x2C02:004
(P351.04)
Motor parameter (ASM): Slip frequency x.x Hz (Read only) general U16 10 - -
0x2C03:005 D-axis inductance Ld 23.566 mH * MCTRL U32 1000 P -
0x2C03:006 Q-axis inductance Lq 23.566 mH * MCTRL U32 1000 P -
0x2C10:001 HF amplitude 50.0 V MCTRL U16 10 P -
0x2C10:008 HF injecon range 6.0 % MCTRL U16 10 P -
0x2C13 SLSM-PSM low speed method Carrier based [1] MCTRL U8 1 P -
0x2D40:002 Device
ulisaon ixt: Power unit warning threshold 95 % general U16 1 P -
0x2D40:004
(P135.04)
Device ulisaon ixt: Device actual ulisaon x % (Read only) general U16 1 O t
0x2D40:005
(P135.05)
Device ulisaon ixt: Device ulisaon (i*t): Error
response
Fault [3] general U8 1 P -
0x2D44:001
(P350.01)
Overspeed monitoring: Threshold 8000 rpm general U16 1 P -
0x2D44:002
(P350.02)
Overspeed monitoring: Response Fault [3] general U8 1 P -
0x2D45:001
(P310.01)
Motor phase failure detecon: Response - Motor
phase 1
No response [0] general U8 1 P -
0x2D45:002
(P310.02)
Motor phase failure detecon: Current threshold 5.0 % general U8 10 P -
0x2D45:003
(P310.03)
Motor phase failure detecon: Voltage threshold 10.0 V general U16 10 P -
0x2D46:001
(P353.01)
Overcurrent monitoring: Threshold 6.8 A * general U16 10 P -
0x2D46:002
(P353.02)
Overcurrent monitoring: Response Fault [3] general U8 1 P -
0x2D4B:001
(P308.01)
Motor overload monitoring (i²*t): Maximum
ulisaon [60 s]
150 % general U16 1 P -
0x2D4B:002
(P308.02)
Motor overload monitoring (i²*t): Speed
compensaon
On [0] general U8 1 P -
0x2D4B:003
(P308.03)
Motor overload monitoring (i²*t): Response Fault [3] general U8 1 P -
0x2D4B:005 Motor overload monitoring (i²*t): Thermal load - (Read only) general U16 1 - -
* Default seng dependent on the model.