MultiSmart Installation & Operation Manual
Example 2:
A low level fuel warning is required. A resistive fuel gauge is connected to digital input 16. A resistance of
less than 500 ohms indicates low fuel remaining. A 10 second activation delay is required to prevent false
triggering. Pump operation is not affected by the fault.
1. Set the Source
Navigate to:
• Scroll down to General fault 1
• Press Assign
• Scroll down to Digital Input 16
• Press Select
• Press Back, Save and the Home key
2. Set the other Parameters
Navigate to:
• Scroll down to General fault 1
• Press Configure
• Enter the new fault description – Low Fuel Warning
• Scroll down to Act Delay and enter 10
• Scroll down to Pumps Unavailable and press Toggle to uncheck the box
• Press Save and the Home key
Page 128 of 260 MultiSmart_IO_Manual_R20