EasyManua.ls Logo

MultiTrode MultiSmart - Well Faults List; Analog Input Faults List

MultiTrode MultiSmart
260 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
MultiSmart Installation & Operation Manual
Fault Name Description
Default
Setting
Default
Status
Section
Reference
percentage of the expected flow, to give a warning to the operator
IO Unit Analog Inputs
IO Unit 1 Ain 1 Over Range
Analog input current is greater than the specified maximum
20mA
On
-
IO Unit 1 Ain 1 Under Range
Analog input current is less than the specified minimum
4mA
On
-
IO Unit 1 Ain 2 Over Range
Analog input current is greater than the specified maximum
20mA
On
-
IO Unit 1 Ain 2 Under Range
Analog input current is less than the specified minimum
4mA
On
-
Generator faults
(No default Sources are linked to these faults)
Generator Running
Generator supply is currently being used
-
Off
5.4.3.4
Generator Fault
Generator is faulty
-
Off
5.4.3.4
Rain Gauge Fault
A predefined fault for a rain gauge
-
Off
-
NOTES:
1. The Low Range Limit is found under: Advanced / IOModule / Unit / Unit 01 / Probe / Probe01 / Duo Probe / Low Range Limit.
2. These are the default inputs only when Thermal/Seal inputs are selected as part of the Setup Wizard.
3. These are the default inputs only when Flygt FLS inputs are selected as part of the Setup Wizard.
4. These faults are specific to each profile.
5. The Inhibit faults (Station & Pump) can be overridden by a digital input (if configured) (e.g. Station Inhibit Override or Pump x Inhibit))
Page 240 of 260 MultiSmart_IO_Manual_R20

Table of Contents

Other manuals for MultiTrode MultiSmart