EasyManuals Logo

Notifier AFP-200 Installation Manual

Notifier AFP-200
196 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #127 background imageLoading...
Page #127 background image
The Main Power Supply Power Supply Calculations
AFP-200 PN 15511:H2 10/14/2002 127
A.3 The Main Power Supply
The control panel's main power supply can supply a total of 5.0 A in alarm and 1.0 A in
standby (Non-Alarm condition). The current available for powering external devices,
however, is subject to lower limits as shown in Figure 126 and Figure 127.
A.3.1 Current Limitations in Standby
Current for operating an external device in standby (Non-Alarm) is subject to the
following limitations:
1. Non-resettable power (TB1, terminals 3 and 4) and resettable power (TB1,
terminals 5 and 6) are limited to a combined total of 0.5 A. Using Table 47,
Calculation Column 1, verify that the combined subtotal of rows 4 and 5 is less
than 0.5 A.
2. The total power supply load is limited to 1.0 A. Using Table 47, verify that the
total of Calculation Column 1 is less than 1.0 A.
Figure 126 TB1 Standby Current Limitations
A.3.2 Current Limitations in Alarm – System Operation on
Primary Power
Current for operating external devices in alarm is subject to the following limitations:
1. High ripple power (TB1, terminals 1 and 2) is limited to 1.5 A. Using Table 47
Calculation Column 2, verify that the subtotal of row 4 is less than 1.5 A.
2. Non-resettable power (TB1, terminals 3 and 4) and resettable power (TB1,
terminals 5 and 6) are limited to a combined total of 0.5 A. Using Table 47
Calculation Column 2, verify that the subtotal of rows 5 and 6 combined is less
than 0.5 A.
3. The maximum load on NAC 1 (TB1, terminals 1 and 2) cannot exceed 2.5 A.
Using Table 47 Calculation Column 2, verify that the subtotal of row 7 is less than
2.5 A.
4. The maximum combined load on NAC 2, NAC 3, and NAC 4 (TB2,
terminals 3-8) cannot exceed 2.5 A. Using Table 47 Calculation Column 2, verify
that the subtotal of row 8, 9, and 10 is less than 2.5 A.
5. The total power supply load is limited to 5.0 A. Using Table 47, verify that the
subtotal for Calculation Column 2 is less than 5.0 A.
Figure 127 TB1 and TB2 Alarm Current Limitations
1
23456
0.5 A combined
TB1
1.0 A Total System
1
2345678
1
23456
0.5 A combined
2.5 A
5.0 A Total System
TB2
2.5 A combined
TB1
1.5 A
Technical Manuals Online! - http://www.tech-man.com

Table of Contents

Other manuals for Notifier AFP-200

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Notifier AFP-200 and is the answer not in the manual?

Notifier AFP-200 Specifications

General IconGeneral
Control Panel TypeAddressable Fire Alarm Control Panel
Auxiliary Power Output24 VDC, 500 mA
Operating Temperature32°F to 120°F (0°C to 49°C)
Display80-character LCD
Power Supply120 VAC, 60 Hz
Capacity198 addressable devices
Notification Appliance Circuits2
Relay Contacts3 (Form-C)
Relative Humidity93% non-condensing

Related product manuals