How to Operate the Control Panel Operation
AFP-200 PN 15511:H2 10/14/2002 107
4.3.1 How to Operate the Panel in Normal Operation
“Normal operation” refers to a control panel that is operating normally—no alarms or
troubles in the system and the “All Systems Normal” message appears in the LCD
display. Figure 100 shows a typical screen that appears with the control panel in normal
operation:
Figure 100 Typical Display Message During Normal Operation
The control panel does the following functions at regular intervals when in normal
operation:
Polls all devices connected to the SLC and the four NAC/Panel Circuits for valid
replies, alarms, supervisory, and trouble signals
Checks for power supply troubles and batteries every 10 seconds
Sends a supervisory query on the LCD-80 interface and verifies proper response
Refreshes the LCD display and Terminal Mode LCD-80 display and updates time
Scans the programming keypad for System Reset or Enter
Auto tests detectors
Tests system memory
4.3.2 How to Operate a Panel with a Trouble Condition
What is a Trouble Condition?
A control panel indicates a trouble condition when a trouble—for example, a short
circuit or ground fault—exists in the fire alarm system. If all troubles clear and no
supervisory or fire alarms exist in the system, the control panel returns to a normal
operation, and sends an “All Systems Normal” message to the LCD display, LCD-80,
History buffer, and printer. This trouble restore occurs even if the troubles were never
acknowledged (auto restore).
During a Trouble operation the control panel does the following:
YOUR@CUSTOM@MESSAGE
HERE@(40@CHARACTERS)
ALL@SYSTEMS@NORMAL
11:13A@@SUN@12/25/97
Custom message area
“All Systems Normal”
message
ENTER
ACKNOWLEDGE
STEP
ALARM
SILENCE
DRILL
HOLD 2 SECONDS
SYSTEM
RESET
AC POWER
FIRE
ALARM
PRE-ALARM
WAR NING
SUPERVISORY
ALARM
SILENCE
SYSTEM
TROUBLE
DET MOD
12
3
4
5
6
7
89
#
A
B
C
D
E
F
G
H
I
J
K
L
M
N
O
P
R
S
T
U
V
W
X
Y
Q
Z
-
/
.
ALL SYSTEMS NORMAL
09:45A THU 06/18/97
M
e
m
b
rn
e
Operator Keys (4)
System Status
LED Indicators (6)
Enter and Cursor
keys
Programming
Keypad
Technical Manuals Online! - http://www.tech-man.com

Table of Contents

Other manuals for Notifier AFP-200

Related product manuals