Programming How to Enter Program Change
78 AFP-200 PN 15511:H2 10/14/2002
3.4.4 How to Edit or Delete a Point (2=POINT)
Purpose
A point is a detector or module connected to the SLC or a device connected to one of
the four panel circuits. The Point Programming (Point) option lets you do the
following:
Modify program information for a detector, module, or panel circuit point
Delete a detector or module point from the program
This section contains instructions using the Point Programming option to do the
following tasks:
Table 19 Point Programming Topics
How to Select a Point
To select a point, follow these steps:
1. From the Program Change screen (Figure 53 on page 71), press the 2 key (Point) to
display the Point Programming Entry screen (Figure 64).
Figure 63 Point Programming Screen
Task Covers the following
Refer to
page
How to Select a Point to modify or delete
a How to display a detector, module, or
panel circuit point so you can modify
or delete it
75
How to Program an Intelligent Detector
a
a. To do this task, the device must be installed and programmed using the Autoprogram
option.
How to modify program information
for an addressable, intelligent
detector
80
How to Program a Monitor Module
a How to modify program information
for a monitor module
81
How to a Program a Control or Relay
Module
a
How to modify program information
for a control or relay module
83
How to Program a Panel Circuit How to modify program information
for any of the four NAC or Panel
Circuits
84
How to Delete a Detector or Module
Point
b
b. Deleting a point only deletes the point from program memory—not the device. For
instructions on removing a device, refer to “How to Remove a Device from the
Program” on page 76.
How delete a detector or module point
from the program
84
Program Change
Password
POINT@PROG.ENTER:
1 = MODIFY POINT
2 = DELETE POINT
Technical Manuals Online! - http://www.tech-man.com

Table of Contents

Other manuals for Notifier AFP-200

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Notifier AFP-200 and is the answer not in the manual?

Notifier AFP-200 Specifications

General IconGeneral
Control Panel TypeAddressable Fire Alarm Control Panel
Auxiliary Power Output24 VDC, 500 mA
Operating Temperature32°F to 120°F (0°C to 49°C)
Display80-character LCD
Power Supply120 VAC, 60 Hz
Capacity198 addressable devices
Notification Appliance Circuits2
Relay Contacts3 (Form-C)
Relative Humidity93% non-condensing