Specifications System Overview
AFP-200 PN 15511:H2 10/14/2002 27
1.11 Specifications
This section contains electrical specifications for the control panel.
1.11.1 Primary AC Power (TB7)
Primary AC connections are made through TB7 on the AFP-200. Wire size: minimum
14 AWG with 600 VAC insulation.
• AFP-200. 120 VAC, 50/60 Hz, 3.0 A
• AFP-200E. 220/240 VAC, 50/60 Hz, 1.5 A
1.11.2 Battery (lead-acid only)
Maximum Charging Circuit Dual Rate High Charge is 29.1 V @ 0.7 A
Normal Flat Charge is 27.6 V @ 0.5 A
Maximum Battery Capacity 18 AH. (Batteries larger than 12 AH require a BB-17
or other UL-listed battery cabinet.)
1.11.3 Signaling Line Circuit (TB6)
Connections between the control panel and the Signaling Line Circuit (SLC) are
supervised and power-limited.
Voltage 24 VDC nominal, 27.6 VDC Max.
Maximum length 10,000 ft. (3048 m) per channel (NFPA Style 4) or
10,000 ft. (3048 m) total twisted-pair length (NFPA
Style 6 and 7)
Maximum loop current is 250 mA (max short circuit) or 100 mA (normal)
Maximum loop resistance 40 ohms
1.11.4 Notification Appliance and Releasing Circuits (TB2)
The following contains specifications for NACs and releasing circuits available on the
AFP-200 (all circuits are power-limited).
Max. wiring voltage drop 2 VDC
Normal Operating Voltage 24 VDC.
NAC circuit 1 2.5 A
NAC circuits 2-4 2.5 A shared total
Current for all external devices 5.0 A
Optional AVPS-24/AVPS-24E Additional 3.0 A of notification appliance power (see
Appendix J “Expansion Power Supplies”)
Optional APS-6R Additional 6.0 A of notification appliance power (see
Appendix J “Expansion Power Supplies”)
Max. signaling current/circuit 2.5 A
End-of-line resistor 4.7K, 1/2-Watt (PN 71252 UL-listed) for NACs)
Releasing circuits REL-4.7K; for control module — REL-47K