Using the CRT-2 for Alter Status Terminal Interface Protocol
AFP-200 PN 15511:H2 10/14/2002 175
Example Disable the NAC at address 1:
4. Press <E> to Enable or press <D> to Disable; then press <Enter>:
I.4.4 Change Detector Sensitivity Levels
This option lets you change the Alarm and Pre-Alarm levels of any addressable detector
in the system. To do so, follow these steps.
5. From the Alter Status menu, select Sensitivity, option 2:
6. Enter the address of the detector you wish to change. For example, detector 57:
I.4.5 Clear the Verification Counter
Clear Verification, option 3, lets you clear the verification counter for all the
addressable detectors in the system:
I.4.6 Clear the Entire History Buffer
Clear History, option 4, lets you clear the entire history buffer:
B01
b01
W
Press
B01 Now Enabled, Enter E(Enable) / D(Disable) or Esc. to Abort
d or e
W
Press
Det. Sensitivity Enter point: AA, E
2W
Press
D57 now Low sens. Enter H, M, or L to change, Esc. to Abort
57
W
Press
Press Enter to Clear Verification Counts or Esc. to Abort
3W
Press
Press Enter to Clear History or Esc. to Abort
4W
Press