Wiring a Signaling Line Circuit (SLC) Installation
AFP-200 PN 15511:H2 10/14/2002 41
2.9 Wiring a Signaling Line Circuit (SLC)
2.9.1 Overview of SLC Wiring
Communication between the control panel and intelligent and addressable initiating,
monitor, and control devices takes place through a Signaling Line Circuit (SLC). You
can wire an SLC to meet the requirements of NFPA Style 4, Style 6, or Style 7 circuits.
This section covers the topics outlined in Table 9:
Table 9 SLC Wiring Topics
Topics Refer to
Setting an Address for a
monitor, control, or relay
module
Figure 22.
Methods for terminating
wiring leaving the
control panel
“SLC Shield Termination” on page 43.
Wire Requirements for
a Two-wire SLC
“Wire Requirements for a Two-wire SLC” on page 45, which covers:
Loop resistance for a Two-wire SLC.
Total wiring length for a Two-wire SLC.
Typical Wiring for a Two-wire SLC.
Wire Requirements for
a Four-wire SLC
“Wire Requirements for a Four-wire SLC” on page 46, which covers:
Loop resistance for a Four-wire SLC.
Total wiring length for a Four-wire SLC.
Typical Wiring for a Four-wire SLC.
Wiring an ISO-X
Isolator Module
“Wiring an Isolator Module (ISO-X)” on page 49, which covers:
Description of an ISO-X Module
Isolating a Branch of a Two-wire SLC
Wiring a Conventional
Initiating Device Circuit
(IDC)
“Wiring an IDC with Monitor Modules” on page 50, which covers:
Description of Monitor Modules
Wiring a Two-wire or Four-wire IDC.
Wiring Notification
Appliance Circuits
(NACs)
“SLC Wiring with Control Modules” on page 57, which covers:
Description of control/relay modules
Wiring a Relay Module
Wiring a Control Module
Wiring a Two-wire NAC (Style Y)
Wiring a Four-wire NAC (Style Z)
Wiring an Intelligent
Detector
“SLC Wiring with an Intelligent Detector” on page 59
Wiring an Addressable
Manual Pull Station
“SLC Wiring with an NBG-12LX Addressable Manual Pull Station”
on page 60
Technical Manuals Online! - http://www.tech-man.com

Table of Contents

Other manuals for Notifier AFP-200

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Notifier AFP-200 and is the answer not in the manual?

Notifier AFP-200 Specifications

General IconGeneral
Control Panel TypeAddressable Fire Alarm Control Panel
Auxiliary Power Output24 VDC, 500 mA
Operating Temperature32°F to 120°F (0°C to 49°C)
Display80-character LCD
Power Supply120 VAC, 60 Hz
Capacity198 addressable devices
Notification Appliance Circuits2
Relay Contacts3 (Form-C)
Relative Humidity93% non-condensing