How to Enter Program Change Programming
AFP-200 PN 15511:H2 10/14/2002 71
3.4 How to Enter Program Change
To enter Program Change mode, follow these steps:
1. Press the
ENTER key to enter programming mode and the LCD display shows the
Programming Entry screen:
Figure 51 Programming Entry Screen
2. Press the 1 key and the following screen appears in the LCD display:
Figure 52 Password Entry Screen
3. Enter your Program Change password. The control panel enters Program Change.
The Program Change options appear in the LCD display as shown in Figure 53:
Figure 53 Program Change Screen
In Program Change, the control panel trouble relay activates—but the panel
sounder does not activate, and the System Trouble LED flashes.
The System Trouble LED
remains flashing throughout
all Program Change
operations.
4. Select a Program Change option by pressing the numeric key (0-8) that matches
the option. To exit Program Change and return to the Program Entry screen, press
the
BACKSPACE key.
1=PROGRAMMING
2=READ@STATUS@ENTRY
(BACKSPACE@TO@ABORT)
ENTER@PROG@OR@STATUS
PASSWORD,@THEN@ENTER.
(BACKSPACE@TO@ABORT)
0=CLR@1=AUTO@2=POINT
3=PASSWD@4=MESSAGE
5=ZONES@6=SPL@ZONES
7=SYS@8=CHECK@PRG
Technical Manuals Online! - http://www.tech-man.com

Table of Contents

Other manuals for Notifier AFP-200

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Notifier AFP-200 and is the answer not in the manual?

Notifier AFP-200 Specifications

General IconGeneral
Control Panel TypeAddressable Fire Alarm Control Panel
Auxiliary Power Output24 VDC, 500 mA
Operating Temperature32°F to 120°F (0°C to 49°C)
Display80-character LCD
Power Supply120 VAC, 60 Hz
Capacity198 addressable devices
Notification Appliance Circuits2
Relay Contacts3 (Form-C)
Relative Humidity93% non-condensing