Installation Preparing for Installation
30 AFP-200 PN 15511:H2 10/14/2002
Section 2 Installation
2.1 Preparing for Installation
2.1.1 Unpacking the System
Carefully unpack the system and inspect for shipping damage.
Select a location for the control panel in a clean, dry, vibration-free area with moderate
temperature.
2.1.2 Installation Notes
Before installing the fire alarm system, read the following:
Install the system in a readily accessible area with sufficient room to easily install
and maintain the control panel.
Locate the top of the cabinet approximately 60 inches (1.524 m) above the floor
with the hinge mounting on the left.
Count the number of conductors needed for all devices and find the appropriate
knockouts.
Review the installation precautions at the front of this manual.
All wiring must comply with the National and/or Local codes for fire alarm
systems.
Do not draw wiring into the bottom 9 inches (22.86 cm) of the cabinet, except
when using the BB-17. This prevents interference between the power supply and
batteries.
2.1.3 Standards and Codes
In addition, installers should be familiar with the following standards:
NEC Article 300 Wiring Methods.
NEC Article 760 Fire Protective Signaling Systems.
Applicable Local and State Building Codes.
Requirements of the Local Authority Having Jurisdiction.
Technical Manuals Online! - http://www.tech-man.com

Table of Contents

Other manuals for Notifier AFP-200

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Notifier AFP-200 and is the answer not in the manual?

Notifier AFP-200 Specifications

General IconGeneral
Control Panel TypeAddressable Fire Alarm Control Panel
Auxiliary Power Output24 VDC, 500 mA
Operating Temperature32°F to 120°F (0°C to 49°C)
Display80-character LCD
Power Supply120 VAC, 60 Hz
Capacity198 addressable devices
Notification Appliance Circuits2
Relay Contacts3 (Form-C)
Relative Humidity93% non-condensing