Installation Wiring a Signaling Line Circuit (SLC)
56 AFP-200 PN 15511:H2 10/14/2002
2.9.11 Wiring a Notification Appliance Circuit (NAC) or
Control Circuit
Control and Relay Module Overview
The FCM-1 is an addressable module that controls a Notification Appliance Circuit
(NAC). Use the FCM-1 to route 24 VDC NAC Power for NFPA Style Y (Class B) and
NFPA Style Z (Class A) notification circuits. Figure 38 shows control module
connections.
Figure 38 FCM-1 Control Module Connections
The FRM-1 is an addressable module which includes a Form-C dry contact relay which
can be used to activate a variety of output circuits. Figure 39 shows relay module
connections.
Figure 39 FRM-1 Relay Module Connections
Ratings for the dry contacts on a Form-C relay module are:
Resistive: 3.0 A @ 30 VDC max Non-coded application
Further rating information is available in the module document and data sheet.
90
81
72
63
54
Style D NAC (+)
Style D NAC (–)
Style B NAC (–)
Style B NAC (+)
no connection
no connection
SLC (–)
SLC (+)
24 VDC Power (–)
24 VDC Power (+)
Note: Polarity shown in alarm condition
8
9
10
11
12
13
14
15
0
1
2
3
4
5
6
7
8
9
0
1
2
3
4
5
6
7
TENS
ONES
LOOP
LOOP ADDRESS
ADDRESS
8
9
7
6
5
9
8
7
6
5
0
1
2
3
4
4
3
2
1
0
TENS
ONES
8
9
0
1
2
3
4
5
6
7
8
9
10
11
12
13
14
150
1
2
3
4
5
6
7
8
9
7
6
5
9
8
7
6
5
0
1
2
3
4
4
3
2
1
0
LOOP
LOOP
SLC
SLC-frmC.cdr
FRM-1
NO
C
NC
NO
C
NC
To next device
on SLC
From FACP or previous device on SLC loop
SLC (+) TB6-3
SLC (–) TB6-5
Refer to the installation
instruction sheet supplied with
the control module for
additional information.