EasyManuals Logo

Omron CQM1 User Manual

Omron CQM1
312 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #183 background imageLoading...
Page #183 background image
164
Sensitivity Adjustment Section 5-2
Teaching for Position Control
1,2,3... 1. Place the sensor head in the sensing range of the sensor.
2. Connect the CQM1-TU001 to the CQM1-SEN01.
3. Set the module selector to the number of the sensor module on which
teaching will be performed.
4. Set the mode setting selector of the CQM1-TU001 to SET.
5. Press the teaching button. The teaching indicator (red) will be lit.
6. Move the object to the position where you want to turn ON the output and
press the teaching button. If teaching is successful, the teaching indicator
will turn from red to green.
7. Do not move the sensing object and press the teaching button a third time.
If teaching is successful, the teaching indicator will turn from green to or-
ange.
8. Set the mode selector to RUN to complete the sensitivity setting on the
E3X-MA11. If teaching is unsuccessful, the teaching indicator (red) will
flash, in which case make sure that the sensor cable is connected, change
the position of the object and the sensing distance that have been set, and
repeat from step 5.

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Omron CQM1 and is the answer not in the manual?

Omron CQM1 Specifications

General IconGeneral
ModelCQM1
I/O CapacityUp to 256 I/O points
Programming LanguageLadder Logic
Timer/Counter128 timers/counters
Operating Temperature0 to 55°C
Humidity10 to 90% RH (non-condensing)
Power Supply24 VDC or 100-240 VAC
Communication PortsRS-232C
Memory Capacity3.2K words
Instruction SetBasic and advanced instructions
MemoryRAM (battery-backed)
Program Memory3.2K words
Storage Temperature-20 to 75°C

Related product manuals