273
Specifications Section 3-2
3-2 Specifications
General Specifications The general specifications of the CQM1-TC00@/TC10@ conform to those of
the CQM1H/CQM1 Series.
Performance Specifications
Dimensions All dimensions are in millimeters.
Item Specification
Input sensors and set
point ranges
Sensors used with thermo-
couples
CQM1-TC00@ K: –200 to 1,300 °C (–300 to 2,300 °F)
CQM1-TC00@ J: –100 to 850 °C (–100 to 1,500 °F)
Sensors used with platinum
resistance thermometers
CQM1-TC10@ JPt100: –99.9 to 450.0 °C (–99.9 to 800.0 °F)
CQM1-TC10@ Pt100: –99.9 to 450.0 °C (–99.9 to 800.0 °F)
Number of control loops Two (either 1 or 2 loops can be used)
Control output NPN or PNP output with short-circuit protection
Power supply voltage: 24 VDC
+10%
/
–15%
Maximum switching capacity: 100 mA per output
Leakage current: 0.3 mA max.
Residual voltage: 3.0 V max.
Control mode ON/OFF or advanced PID control (2 degrees of freedom)
Setting and display accuracy CQM1-TC00@: (Process value ±1% or ±3 °C, whichever is
larger) ±1 digit max.
CQM1-TC10@: (Process value ±1% or ±2 °C, whichever is
larger) ±1 digit max.
Hysteresis 0.8 °C/°F
Proportional band 40.0 °C/°F
Derivative time 240 s
Integral time 40 s
Control period 20 s
Sampling period 1 s
Output refresh period 1 s
Current consumption 220 mA max. at 5 VDC
Weight 200 g max.
Dimensions 32 x 110 x 107 mm (W x H x D)