221
Commands and Responses Section 7-3
Parameter
Response If the correct command code or parameter is set to the output word, the com-
mand code or parameter is set to the input word as a response.
If the wrong command code or parameter is set to the output word, one of the
following error codes will be set to the input word.
E000: This error code will be set to the input word if a nonexisting command
code is used.
E001: This error code will be set to the input word if the parameter is not
within the range covered by the Unit.
7-3-4 Operation Mode B Read
This command is used to read the data that has been input in operation mode
B.
Command
Command Code
Parameter Parameters are not used with this command.
Zero shift value storage area
0: Unchanged
1: RAM (factory-set)
2: Nonvolatile memory
Number of mean value processings
0: Unchanged
1: 1
2: 2
3: 4 (factory-set)
4: 8
5: 16
Input sampling speed
0: Unchanged
1: Fast
2: Slow (factory-set)

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Omron CQM1 and is the answer not in the manual?

Omron CQM1 Specifications

General IconGeneral
ModelCQM1
I/O CapacityUp to 256 I/O points
Programming LanguageLadder Logic
Timer/Counter128 timers/counters
Operating Temperature0 to 55°C
Humidity10 to 90% RH (non-condensing)
Power Supply24 VDC or 100-240 VAC
Communication PortsRS-232C
Memory Capacity3.2K words
Instruction SetBasic and advanced instructions
MemoryRAM (battery-backed)
Program Memory3.2K words
Storage Temperature-20 to 75°C