Nomenclature Section 2-3
Temperature Ranges
Units for Thermocouples The setting ranges are shown in the following table. Indication ranges are the
setting range
±20°C/°F. (See note 1.)
Units for Platinum
Resistance Thermometers
The setting ranges are shown in the following table. Indication ranges are the
setting range
±20 °C/°F. (See note 1.)
Note 1. For binary indications, a sensor error (E400) will occur if the specified
range is exceeded. In Auto Mode, the output for the corresponding loop will
turn OFF if this error occurs.
2. For BCD indications, the indicated values will be clamped to the upper or
lower limit between the upper or lower limit of the setting range and the val-
ues that will cause a sensor error (E400),
0.1
°C/°F Indications: Lower limit = –99.9, Upper limit = 999.9
0.01
°C Indications: Lower limit = –9.99, Upper limit = 99.99
3. The lower limit of indications for B thermocouples is 0
°C/°F.
Code
No.
Input
type
°C °F
Binary
(4-digit Hex)
BCD Binary
(4-digit Hex)
BCD
0 K FF38 to FFFF to 0514
(–200 to –1 to 1300)
F200 to 1300
(–200 to 1300)
FED4 to FFFF to 08FC
(–300 to –1 to 2300)
F300 to 2300
(–300 to 2300)
1 K 0000 to 1388
(0.0 to 500.0)
0000 to 5000
(0.0 to 500.0)
0000 to 2328
(0.0 to 900.0)
0000 to 9000
(0.0 to 900.0)
2 J FF9C to FFFF to 0352
(–100 to –1 to 850)
F100 to 0850
(–100 to 850)
FF9C to FFFF to 05DC
(–100 to –1 to 1500)
F100 to 1500
(–100 to 1500)
3 J 0000 to 0FA0
(0.0 to 400.0)
0000 to 4000
(0.0 to 400.0)
0000 to 1D4C
(0.0 to 750.0)
0000 to 7500
(0.0 to 750.0)
4 T F830 to FFFF to 0FA0
(–200.0 to –0.1 to 400.0)
F999 to 4000 (See
note 2.)
(–99.9 to 400.0)
F448 to FFFF to 1B53
(–300.0 to –0.1 to 700.0)
F999 to 7000 (See
note 2.)
(–99.9 to 700.0)
5 L FF9C to FFFF to 0352
(–100 to –1 to 850)
F100 to 0850
(–100 to 850)
FF9C to FFFF to 05DC
(–100 to –1 to 1500)
F100 to 1500
(–100 to 1500)
6 L 0000 to 0FA0
(0.0 to 400.0)
0000 to 4000
(0.0 to 400.0)
0000 to 1D4C
(0.0 to 750.0)
0000 to 7500
(0.0 to 750.0)
7 R 0000 to 06A4
(0 to 1700)
0000 to 1700
(0 to 1700)
0000 to 0BB8
(0 to 3000)
0000 to 3000
(0 to 3000)
8 S 0000 to 06A4
(0 to 1700)
0000 to 1700
(0 to 1700)
0000 to 0BB8
(0 to 3000)
0000 to 3000
(0 to 3000)
9 B (See
note 3.)
0064 to 0708
(100 to 1800)
0100 to 1800
(100 to 1800)
012C to 0C80
(300 to 3200)
0300 to 3200
(300 to 3200)
Code
No.
Input
type
°C °F
Binary
(4-digit Hex)
BCD Binary
(4-digit Hex)
BCD
0 Pt100 F830 to FFFF to 1964
(–200.0 to –0.1 to
650.0)
F999 to 6500 (See note
2.)
(–99.9 to 650.0)
F448 to FFFF to 2EE0
(–300.0 to –1 to 1200.0)
F999 to 9999 (See note
2.)
(–99.9 to 999.9)
1 JPt100 F830 to FFFF to 1964
(–200.0 to –0.1 to
650.0)
F999 to 6500 (See note
2.)
(–99.9 to 650.0)
F448 to FFFF to 2EE0
(–300.0 to –1 to 1200.0)
F999 to 9999 (See note
2.)
(–99.9 to 999.9)
2 Pt100 F830 to FFFF to 61A8
(–20.00 to –0.01 to
250.00)
F999 to 9999 (See note
2.)
(–9.99 to 99.99)
Do not set. (See note 4.)
3 JPt100 F830 to FFFF to 61A8
(–20.00 to –0.01 to
250.00)
F999 to 9999 (See note
2.)
(–9.99 to 99.99)
4 to 9 --- Do not set. (See note 4.)