EasyManua.ls Logo

Omron SYSDRIVE 3G3FV

Omron SYSDRIVE 3G3FV
400 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
1-5
Custom V/f pattern can be set.
H Frequency References
The following five types of frequency references can be used to control the output frequency of the
Inverter.
S Numeric input from the Digital Operator
S Voltage input within a range from 0 to 10 V
S Voltage
input within a range from 0 to
±
10 V (With minus
voltage, rotation is in the opposite direc
-
tion of the run command.)
S Current input within a range from 4 to 20 mA
S Input by Optional Card
The Inverter can be set to use any of the above types by designating it with parameters.
A maximum of eight frequency references can be registered in the Inverter. Including inching, this
enables multi-step speed operation with up to nine speed steps via remote multi-step reference
inputs.
H PID Control
The Inverter has a PID control function, enabling easy follow-up control.
Follow-up
control is a control method
in which the Inverter varies the output frequency to match the
feedback value from the sensor with the set target value.
Follow-up control can be applied to a variety of control operations, depending on the contents
detected by the sensor.
PID control is available for the following applications.
S Speed control: With
a speed sensor
, such as a
tacho-generator
, the Inverter regulates the
rotation
speed of the motor regardless of the load of the motor or synchro
-
nizes the rotation speed of the motor with that of another motor.
S Pressure control: With a pressure sensor, the Inverter performs constant pressure control.
S Flow-rate control: By sensing the flow rate of a fluid, the Inverter performs precise flow-rate
control.
S Temperature control: With a temperature sensor, the Inverter performs temperature control by
fan speed.
H Zero-servo Control
This function is valid with vector control (with PG).
Even
at a motor speed of zero (0
Hz), a torque of 150% of the motor
s rated torque can be generated
and the average servomotor holding power (stopping power) can be obtained.
H Speed Control By Feedback
This function is valid with PG.
An
optional PG Speed Control Card be used to enable feedback control for
speeds, thereby improving
speed control accuracy.
Introduction Chapter
1

Table of Contents

Related product manuals