7-21
7-2-3 Reference Parameters List
H Preset Reference: d1
Para
meter
Name
Description Setting
range
Default
setting
Chan-
ges
Control
mode
Page
meter
No.
Display
name
range setting ges
during
opera-
tion
V/f
control
V/f
with
PG
Open
loop
vector
Flux
vector
d1-01
Frequency
reference 1
Sets the frequency reference in
the units used in o1-03
(f f dil/t
0 to
max.
f
6.00 OK Q Q Q Q 5-10
Preset
Reference
1
(frequency reference display/set
units.) The default setting unit
for o1-03 is Hz.
fre-
quency.
d1-02
Frequency
reference 2
The frequency reference when
the multi-function input
lti t d f 1”
0.00 OK Q Q Q Q 5-10
Preset
Reference
2
“multi-step speed reference 1”
is ON.
d1-03
Frequency
reference 3
The frequency reference when
the multi-function input
lti t d f 2”
0.00 OK Q Q Q Q 5-10
Preset
Reference
3
“multi-step speed reference 2”
is ON.
d1-04
Frequency
reference 4
The frequency reference when
the multi-function input
lti t d f 1
0.00 OK Q Q Q Q 5-10
Preset
Reference
4
“multi-step speed reference 1,
2” is ON.
d1-05
Frequency
reference 5
The frequency reference when
the multi-function input
lti t d f 3”
0.00 OK B B B B 5-10
Preset
Reference
5
“multi-step speed reference 3”
is ON.
d1-06
Frequency
reference 6
The frequency reference when
the multi-function input
lti t d f 1
0.00 OK B B B B 5-10
Preset
Reference
6
“multi-step speed reference 1,
3” is ON.
d1-07
Frequency
reference 7
The frequency reference when
the multi-function input
lti t d f 2
0.00 OK B B B B 5-10
Preset
Reference
7
“multi-step speed reference 2,
3” is ON.
d1-08
Frequency
reference 8
The frequency reference when
the multi-function input
lti t d f 1
0.00 OK B B B B 5-10
Preset
Reference
8
“multi-step speed reference 1,
2, 3” is ON.
d1-09
Jog
frequency
reference
The reference frequency when
the multi-function inputs, “Jog
reference frequency selection,”
“FJOG d d “RJOG
6.00 OK Q Q Q Q 5-10
Jog
Reference
qy ,
“FJOG command,” and “RJOG
command” are ON.
Parameter Lists Chapter