7-3
7-1 Initialize Mode Parameters
Para
Control mode
Page
meter
No.
Display
name
range setting
e dur
-
ing
opera-
tion
V/f
control
V/f
with
PG
Open
loop
vector
Flux
vector
A1-00
Display
Language
Used to select the language
displayed on the Digital
Operator
0: English
1: Japanese
2: German
0 to 6
1 OK Q Q Q Q 3-18
Select
Language
4: Italian
5: Spanish
6: Portuguese
Note: This parameter is not ini
-
tialized by the initialize
operation.
A1-01
Access
Level
Used to set the parameter
access level (set/read.)
0:
Monitoring only (Displays
only Operation mode and
Initialize mode)
1: Used to select user
0 to 4
2 OK Q Q Q Q 3-18
Access
Level
parameter
(Parameters A2-01 to A2-32
only can be set/read.)
2: QUICK-START
3: BASIC
4: ADVANCED
A1-02
Select
Control
Method
Used to select the control
method for the Inverter
0:
V/f control
1:
V/f with PG
2:
Open loop vector
0 to 3
2 NO Q Q Q Q 3-19
Control
Method
3: Flux vector
Note:
This parameter is not ini
-
tialized by the initialize
operation.
A1-03
Initialize
Used to initialize the parameters
using the specified method.
0:
No initializing
1110:
Initializes using the
0 to
3330
0 NO Q Q Q Q 3-20
Init
Parameters
User parameters
2220:
Initializes using a
two-wire sequence.
3330:
Initializes using a
three-wire sequence.
A1-04
Password
When a password has been set
in A1-05 this function write
protects the password input
section of the Operation mode
parameter.
0 to
9999
0 NO Q Q Q Q 3-22
Enter
Password
Note:
If the password is
changed, parameters
A1-01 to A1-03 and A2-01
to A2-32 can no longer be
changed. (Program mode
parameters can be
changed.)
Parameter Lists Chapter
7