7-13
7-2-2 Tuning Parameters
H Acceleration/Deceleration: C1
Para
meter
Name
Description Setting
range
Default
setting
Chan-
ges
Control
mode
Page
meter
No.
Display
name
range setting ges
during
opera-
tion
V/f
control
V/f
with
PG
Open
loop
vector
Flux
vector
C1-01
Accelera-
tion time 1
Sets the acceleration time to
accelerate from 0 to the
if
i
0.0 to
6000.0
(S
10.0 OK Q Q Q Q 5-12,
5-18
Accelera-
tion T
ime 1
maximum frequency
, in
1-second units.
(See
note.)
C1-02
Decelera-
tion time 1
Sets the deceleration time to
decelerate from the maximum
ft0i1d
OK Q Q Q Q 5-12,
5-18
Decelera-
tion T
ime 1
frequency to 0, in 1-second
units.
C1-03
Accelera-
tion time 2
The acceleration time when the
multi-function input
lti l/d l ti 1” i t
OK B B B B 5-12,
5-18
Accelera-
tion T
ime 2
“multi-accel/decel time 1” is set
to ON.
C1-04
Decelera-
tion time 2
The deceleration time when the
multi-function input
lti l/d l ti 1” i t
OK B B B B 5-12,
5-18
Decelera-
tion T
ime 2
“multi-accel/decel time 1” is set
to ON.
C1-05
Accelera-
tion time 3
The acceleration time when the
multi-function input
lti l/d l ti 2” i t
NO A A A A 5-12,
5-18
Accelera-
tion T
ime 3
“multi-accel/decel time 2” is set
to ON.
C1-06
Decelera-
tion time 3
The deceleration time when the
multi-function input
lti l/d l ti 2” i t
NO A A A A 5-12,
5-18
Decelera-
tion T
ime 3
“multi-accel/decel time 2” is set
to ON.
C1-07
Accelera-
tion time 4
The acceleration time when the
multi-function input
multi accel/decel time 1
and
NO A A A A 5-12,
5-18
Accelera-
tion T
ime 4
“multi-accel/decel time 1” and
“multi-accel/decel time 2” are
set to ON.
C1-08
Decelera-
tion time 4
The deceleration time when the
multi-function input
multi accel/decel time 1
and
NO A A A A 5-12,
5-18
Decelera-
tion T
ime 4
“multi-accel/decel time 1” and
“multi-accel/decel time 2” are
set to ON.
C1-09
Emergency
stop time
The deceleration time when the
multi-function input “Emergency
(fast) stop” is set to ON.
NO B B B B 5-12,
5-18
Fast Stop
Time
(fast)
sto
is
set
to
ON.
Note:
This function can be used
as a stop method when a
fault has been detected.
C1-10
Accelera-
tion/decel-
eration time
units
0:
0.01-second units
1:
0.1-second units
0, 1
1 NO A A A A 5-11,
5-18
Acc/Dec
Units
Parameter Lists Chapter
7