range setting
V/f
Control
V/f
with PG
Open Loop
Vector
Flux
Vector
A1-04 Enter Password 0000 to
9999
--- 0 Quick-start, Basic, or Advanced
Parameter Display name Setting Units Default
Valid access levels
number
range setting
V/f
Control
V/f
with PG
Open Loop
Vector
Flux
Vector
A1-05 Select Password 0000 to
9999
--- 0 Quick-start, Basic, or Advanced
Password Setting Example
The following example shows how to set the password to “1000.”
Key sequence Display Explanation
** Main Menu **
Operation
Displays operation mode.
** Main Menu **
Initialize
Displays initialize mode.
Select Language
English
Puts the Unit in initialize mode.
(Select Language display)
4 times
Enter Password
A1-04= 0
Displays the Enter Password display.
+
Select Password
A1-05= 0
Press and hold the Reset Key and then press the
Menu Key to display A1-05.
Select Password
0000
Selects the parameter so that the leading 0 flashes.
(The digit that can be changed flashes.)
Select Password
1000
Changes the password to 1000.
Entry Accepted
Writes the new setting.
Select Password
A1-05= 1000
Returns to the Select Password display (A1-05).
Enter Password
A1-04= 0
Returns to the Enter Password display (A1-04).
S User Parameters
Parameters
A2-01 through A2-32 specify the parameters that can be
displayed and changed when the
access
level parameter (A1-01) is set to 1. Parameters A2-01 through A2-32 can be changed only in the
Advanced access level and cannot be changed during operation.
Parameter Display name Setting Units Default
Valid access levels
numbers