H2
Digital Outputs
Function selection for multi-function outputs
OK OK OK OK
H3
Analog Inputs
Adjustment/function selection for external analog inputs
OK OK OK OK
H4
Analog Outputs
Adjustment/function selection for multi-function analog
outputs
OK OK OK OK
H5
Serial Com Setup
Not Used. (Do not change this setting.)
--- --- --- ---
Protection
L1
Motor Overload
Sets electrical/thermal functions that protect the motor
. OK OK OK OK
L2 PwrLoss Ridethru
Selects the power-loss processing method.
OK OK OK OK
L3
Stall Prevention
Accel/Decel/Run stall prevention settings and selection
OK OK OK OK
L4
Ref Detection
Frequency detection settings and selection
OK OK OK OK
L5
Fault Restart
Fault restart function settings
OK OK OK OK
L6 T
orque Detection
Sets overtorque detection functions 1 and 2 (by current)
OK OK OK OK
L7 T
orque Limit
Not used. (Can’t be set.)
--- --- OK OK
L8
Hdwe Protection
Hardware overheating and phase loss protection settings
OK OK OK OK
Operator
o1
Monitor Select
Selects the Operator
’
s display and setting methods.
OK OK OK OK
o2 Key Selections Operator’
s key function selection and other parameters
OK OK OK OK
6-2-2 Energy-saving Control Function
The
energy-saving control function is enabled when the energy-saving command (setting 63) has been
set
in a multi-function input (H1-01 through H1-06). Inputting the energy-saving command while there is
a
light load causes the Inverter
’
s output voltage to be reduced and saves energy
. T
urn OFF the energy-
saving command when a normal load is added.
Parameter
b8-01 determines the Inverter
’
s output voltage when
the energy-saving command is input.
Set
this
value as a percentage of the V/f pattern’
s voltage. Parameter L2-04 (the voltage recovery time)
determines
the rate at which the output voltage is changed when the energy-saving command is turned
ON or OFF.
Parameter
b8-02 determines the lower limit frequency for the energy-saving
function. The energy-sav
-
ing command is enabled only when the frequency reference is above this lower-limit and the motor
speed is within the “speed agree” range.
Parameters b8-01 and b8-02 cannot be changed during operation.
Parameter Display name Setting Units Default
Valid access levels
number
range setting
V/f
Control
V/f with
PG
Open Loop
Vector
Flux
Vector
b8-01 Energy Save Gain 0 to 100 % 80
Advanced Not applicable.
b8-02 Energy Save Freq 0.0 to 400.0 Hz 0.0
Advanced Operation Chapter