8-12
8-1-3 Operation Errors
After the parameters have been set, an operation error will occur if there is an invalid
setting or a contradiction between two parameter settings.
It won’t be possible to start the Inverter until the parameters have been set correctly.
(The minor fault output and fault contact output will not operate, either.)
When
an operation error has occurred, refer to the following table to identify and correct
the cause of the errors.
H Operation Error Displays and Incorrect Settings
Display Meaning Incorrect settings
OPE01
kVA Selection
Incorrect Inverter
capacity setting
The Inverter capacity setting doesn’t match the Unit. (Contact
your OMRON representative.)
OPE02
Limit
Parameter setting
range error
The parameter setting is outside of the valid setting range.
OPE03
Terminal
Multi-function input
selection error
One
of
the following errors has been made in the multi-function
input (H1-01 to H1-06) settings:
The same setting has been selected for two or more multi-
function inputs.
An UP or DOWN command was selected independently.
(They must be used together.)
More than two out of the following four items are set.
UP/DOWN commands, Hold Accel/Decel, +Speed/–Speed
commands, and Sample/Hold for analog frequency refer-
ence.
Speed
Search 1 (61)
and Speed Search 2 (62) were selected
at the same time.
External
Baseblock N.O. (8) and External Baseblock N.C. (9)
were selected at the same time.
The UP/DOWN commands (10 and 11) were selected while
PID control (b5-01) was enabled.
The
T
erminal 13/14 Switch (1F) was selected, but the terminal
14
function selector (H3-09) wasn’t set to frequency reference
(1F).
The
+Speed and –Speed commands are not set at the
same
time.
The
NO and NC contacts of an emergency stop input are set at
the same time.
OPE05
Sequence Select
Optional Card
selection error
The Optional Card was selected as the frequency reference
source by setting b1-01 to 3, but an Optional Card isn’t con-
nected.
OPE06
PG Opt Missing
Control mode
selection error
V/f
control with PG feedback was selected by setting
A1-02 to 1,
but a PG Speed Control Card isn’t connected.
Flux
vector
control was selected by setting A1-02 to 3, but a PG
Speed Control Card isn’t connected.
Maintenance Operations Chapter