6-31
6-3-7 Setting/Adjusting Motor Parameters
H Adjusting the V/f Pattern
Normally
it isn’t necessary to adjust the V/f pattern with flux vector control.
Adjust the V/f pattern when
you want to change the maximum frequency, maximum voltage, base frequency, or minimum output
frequency settings.
Parameter Display name Setting Units Default
Valid access levels
*1
number
py
g
range setting
V/f
Control
V/f with
PG
Open Loop
Vector
Flux
Vector
E1-04 Max Frequency 40.0 to 400.0 Hz 60.0 Q Q Q Q
E1-05 Max Voltage 0.0 to 255.0
*2
VAC 200.0
*2
Q Q Q Q
E1-06 Base Frequency 0.0 to 400.0 Hz 60.0 Q Q Q Q
E1-09 Min Frequency 0.0 to 400.0 Hz 0.0 Q Q Q A
Note 1. Q: Quick Start, Basic, or Advanced
A: Advanced only
Note 2. These voltages are for the 200-V class; Double the voltage for 400-V class Inverters.
Note 3. The
default setting for E1-09 depends on the control mode. The default settings shown in the
table are for flux vector control.
Note 4. The three frequency settings must satisfy the following formula:
E1-04 (F
MAX
) E1-06 (F
A
) > E1-09 (F
MIN
)
V/f Pattern
Output voltage (V)
Frequency (Hz)
V
MAX
(E1-05)
F
MIN
(E1-09)
F
A
(E1-06)
F
MAX
(E1-04)
D Units for V/f Pattern Settings
The units used for V/f pattern frequency settings can be changed when flux vector control has been
selected. This parameter cannot be changed during operation.
Parameter Display name Setting Units Default
Valid access levels*
number
py
g
range setting
V/f
Control
V/f with
PG
Open Loop
Vector
Flux
Vector
o1-04 Display Units 0 or 1 --- 0 Not applicable. B
Note B: Basic or Advanced
Display Unit Settings
Setting Function
0 Units: Hz
1 Units: r/min
Advanced Operation Chapter
6