Note 1. The setting units for parameters E1-04, E1-06, and E1-09 can be changed.
Note 2. This function is specific to flux vector control.
H Setting Motor Parameters
The motor parameters (function E2) will all be set automatically when auto-tuning is performed, so it
normally
isn’t necessary to set them manually
. Set these parameters manually if auto-tuning can’t be
completed properly. These parameters cannot be changed during operation.
Set the rated current (A) shown on the motor’s nameplate.
Parameter Display name Setting Units Default
Valid access levels
number
range setting*
V/f
Control
V/f with
PG
Open Loop
Vector
Flux
Vector
E2-01 Motor Rated FLA 0.32 to 6.40 A 1.90 Quick Start, Basic, or Advanced
Note The
setting range is 10% to 200% of the Inverter
’s rated output
current. The default setting de
-
pends
upon the type of Inverter
. (The table shows the default setting for 200-V class, 0.4-kW In
-
verters.)
Calculate
the rated slip (E2-02) from the value shown on the motor
’
s nameplate with the following equa
-
tion and set this value.
Rated slip = rated frequency (Hz) – rated speed (r/min) × number of poles/120
Set
the no-load current (E2-03) at the rated voltage and rated frequency
. Normally this value isn’t shown
on the motor’s nameplate, so it might be necessary to contact the motor manufacturer.
Parameter Display name Setting range Units Default
Valid access levels
number
setting*
V/f
Control
V/f with
PG
Open Loop
Vector
Flux
Vector
E2-02 Motor Rated Slip 0.00 to 20.00 Hz 2.90
Advanced Quick Start, Basic,
E2-03 No-Load Current 0.00 to 2.90
(see note 2)
A 1.20
or Advanced
Note 1. The default setting depends upon the type of Inverter.
(The table shows the default settings for 200-V class, 0.4-kW Inverters.)
Note 2. The setting range is between 0.00 and 0.1 less than the Inverter’s rated current.
Set the number of poles (E2-04) shown on the motor’s nameplate.
Parameter Display name Setting Units Default
Valid access levels*
number
range setting
V/f
Control
V/f with
PG
Open Loop
Vector
Flux
Vector
E2-04 Number of Poles 2 to 48 --- 4 --- Q --- Q
Note Q: Quick Start, Basic, or Advanced
---: Not applicable.
Set the motor’s terminal resistance between U and V, V and W, or W and U.
Usually
the nameplate of the motor does not provide the motor
’
s terminal resistance. Contact the motor
manufacturer for a test report on the motor’s terminal resistance to set the following values.
• Type E insulation: Motor’s terminal resistance (Ω) at 75°C x 0.92
• Type B insulation: Motor’s terminal resistance (Ω) at 75°C x 0.92
Advanced Operation Chapter