EasyManua.ls Logo

Omron SYSDRIVE 3G3FV

Omron SYSDRIVE 3G3FV
400 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
7-44
7-2-7 Protection Parameter Lists
H Motor Overload: L1
Para
meter
Name
Description Set-
tin
g
De-
fault
Chan-
g
es
Control
mode
Page
meter
No.
Display name
ting
rang
e
fa
u
lt
set-
ting
ges
dur-
ing
op-
era-
tion
V/f
con-
trol
V/f
with
PG
Open
loop
vec-
tor
Flux
vec-
tor
L1-01
Motor protection
selection
Sets whether the motor overload
function is enabled or disabled at
electric thermal overload relay
.
0: Disabled
1: Enabled
Note:
In some applications when the
Inverter power supply is turned
of
f, the thermal value is reset,
so even if this
p
arameter is set
0, 1
1 NO B B B B 6-98
MOL Fault Select
so even if this parameter is set
to 1, (Enabled), protection may
not be ef
fective.
When several motors are con
-
nected to one Inverter, set to 0
(Disabled) and ensure that each
motor is installed with a protec
-
tion device.
L1-02
Motor protection
time constant
Sets the electric thermal detection
time in units of seconds.
Note: Usually setting is not necessary.
The default setting is 150%
overload for one minute.
When the motor
s overload re
0.1 to
5.0
1.0 NO B B B B 6-98
MOL T
ime Const
When the motor
s overload re
-
sistance is known, set at the
overload resistance when the
motor is hot started. (Always
leave a margin for error
.)
H Power Loss Ridethrough: L2
Para
meter
Name
Description Setting
range
Default
setting
Chan-
ges
Control
mode
Page
meter
No.
Display
name
range setting ges
during
opera-
tion
V/f
control
V/f
with
PG
Open
loop
vector
Flux
vector
L2-01
Momentary
power loss
selection
0:
Disabled (Undervoltage
fault detection)
1:
Enabled (Restarted when
the power returns within the
time for L2-02. When L2-02
is exceeded, undervoltage
fault detection )
0 to 2
0 NO B B B B 6-99
PwrL
Selection
fault detection.)
2:
Enabled while CPU is
operating. (Restarts when
power returns during control
operations. Does not detect
undervoltage fault.
L2-02
Momentary
power loss
ridethru
Sets the recovery time, when
momentary power loss selection
(L2-01) is set to 1, in units of
d
0.0 to
2.0
0.7
(See
note 1.)
NO B B B B 6-99
PwrL
Ridethru t
() ,
one second.
)
Parameter Lists Chapter
7

Table of Contents

Related product manuals