7-45
Para
meter
No.
PageControl
mode
Chan-
ges
during
opera-
tion
Default
setting
Setting
range
DescriptionNamePara
meter
No.
Page
Flux
vector
Open
loop
vector
V/f
with
PG
V/f
control
Chan-
ges
during
opera-
tion
Default
setting
Setting
range
Description
Display
name
L2-03
Minimum
baseblock
time (BB)
Sets the Inverter
’
s minimum
baseblock time in units of one
second, when the Inverter is
restarted after power loss
ridethrough.
Note:
Sets the time for the mo
-
tor’
s residual volta
e to
0.1 to
5.0
0.5
(See
note 1.)
NO B B B B 6-100
PwrL
Baseblock t
dissipate.
When an overcurrent oc
-
curs when starting a
speed search or DC injec
-
tion braking, increase the
set values.
L2-04
Voltage
restart time
Sets the time required to return
to normal voltage at the
completion of a speed search,
in units of one second.
Note:
Set the time required for a
200 V class Inverter to re
0.0 to
5.0
0.3 NO A A A A 6-100
PwrL V/F
Ramp t
200-V class Inverter to re
-
cover from 0 V to
200 V
AC.
(For the 400-V class In
-
verter
, the time from 0 V
to 400 V
AC.)
L2-05
Under
voltage
detection
level (UV)
Sets the main circuit under
voltage (UV) detection level
(main circuit DC voltage) in V
units.
Note:
Usually setting is not nec
-
essar
. Insert a AC reac
-
150 to
210
(See
note 2.)
190
(See
note 2.)
NO A A A A 6-100
PUV Det
Level
tor and use this function
to lower the main circuit
under voltage detection
level.
L2-06
KEB
deceleration
rate
By decelerating simultaneously
with a momentary power
interruption, this function
produces regenerative energy
and utilizes this energy to
counter the power interruption.
Select the deceleration rate to
be applied after the KEB
command (set value: 65 or 66)
set for multi-function inputs is
input.
Set as a percentage the
deceleration frequency rate for
when the time set in L2 02 has
0.0 to
100.0
0.1 NO A A A A ---
KEB
Frequency
when the time set in L2-02 has
elapsed after KEB command
input.
If 80% is set, deceleration will
be performed taking the time set
in L2-02, up to 80% of the
output frequency when KEB is
input.
If L2-06 is set to 0.0, C1-09 will
automatically decelerate to the
base so that the undervoltage
(UV) of the main circuit will not
be detected.
Note 1. The
default setting depends upon the type
of Inverter
. The values for a 200-V class 0.4-kW
Inverter arre given above.
Note 2. These
are values for a 200-V class Inverter
. V
alues for the 400-V class Inverter are double.
Parameter Lists Chapter
7