7-43
H Serial Communications Setup: H5
Para
meter
Name
Description Setting
range
Default
setting
Chan-
ges
Control
mode
Page
meter
No.
Display
name
range setting ges
during
opera-
tion
V/f
control
V/f
with
PG
Open
loop
vector
Flux
vector
H5-01
Slave
Address
Sets the Slave address for
RS-422/485 communications.
00 to
20
1F NO A A A A ---
Serial
Comm Adr
00: Communications function
disabled.
H5-02
Baud rate
selection
Selects the baud rate for
RS-422/485 communications.
0: 1,200 bps
1: 2 400 b
p
s
0 to 4
3 NO A A A A ---
Serial Baud
Rate
1: 2,400 bps
2: 4,800 bps
3: 9,600 bps
4: 19,200 bps
H5-03
Parity
selection
Selects the parity check
function for RS-422/485
communications.
0 to 2
0 NO A A A A ---
Serial Com
Sel
communications.
0: No parity
1: Odd parity
2: Even parity
H5-04
Operation
for commu
-
nication
timeover
Selects the method of operation
for when it is detected that the
communications time has
elapsed in RS-422/485
communications.
0: Deceleration stop
(C1 02)/F lt
0 to 3
3 NO A A A A ---
Serial Fault
Sel
(C1-02)/Fault
1: Free-run stop/Fault
2: Fast stop (C1-09)/Fault
3: Continue/Alarm
H5-05
Commu-
nications
timeover
detection
selection
Enables or disables the
communications timeover
function in RS-422/485
communications.
0: Disable
0, 1
1 NO A A A A ---
Serial Flt
Dtct
0:
Disable
1: Enable
Parameter Lists Chapter
7