7-42
H Analog Outputs: H4
Para
Control
mode
Page
meter
No.
Display
name
range setting ges
during
opera-
tion
V/f
control
V/f
with
PG
Open
loop
vector
Flux
vector
H4-01
Multi-func-
tion analog
output 1
selection:
terminal 21
Sets the number of the monitor
item to be output (U1-
) from
terminal 21.
Note:
Settings 4, 10, 1
1, 12, 13,
14, 25, 28, 34, and 35
1 to 38
2 NO B B B B 6-96
T
erminal 21
Sel
cannot be set and 29 to
31 are not used.
H4-02
Gain
terminal 21
Sets the multi-function analog
output 1 voltage level gain.
Sets whether the monitor item
0.00 to
2.50
1.00 OK B B B B 6-97
T
erminal 21
Gain
Sets whether the monitor item
output will be output in multiples
of 10 V
.
H4-03
Bias
terminal 21
Sets the multi-function analog
output 1 voltage level bias.
0.0 OK B B B B 6-97
T
erminal 21
Bias
Sets output characteristic
up/down parallel movement as
a percentage of 10 V
.
+10.0
H4-04
Multi-func-
tion analog
output 2
selection:
terminal 23
Sets the number of the monitor
item to be output (U1-
) from
terminal 23.
Note:
Settings 4, 10, 1
1, 12, 13,
14, 25, 28, 34, and 35
1 to 38
3 NO B B B B 6-96
T
erminal 23
Sel
cannot be set and 29 to
31 are not used.
H4-05
Gain
terminal 23
Sets the multi-function analog
output 2 voltage level gain.
Sets whether the monitor item
0.00 to
2.50
0.50 OK B B B B 6-97
T
erminal 23
Gain
Sets whether the monitor item
output will be output in multiples
of 10 V
.
H4-06
Bias
terminal 23
Sets the multi-function analog
output 2 voltage level bias.
0.0 OK B B B B 6-97
T
erminal 23
Bias
Sets output characteristic
up/down parallel movement as
a percentage of 10 V
.
+10.0
H4-07
Analog
output
signal level
selection
Sets the signal output level for
multi-function outputs 1 and 2
(terminals 21, 23.)
0:
0 to +10 V output
1:
0 to
±
10 V output
0, 1
0 NO B B B B 6-97
AO Level
Select
Note:
The optional Analog Mon
-
itor Card may also be
used with this setting.
Parameter Lists Chapter
7