7-14
Para
meter
No.
PageControl
mode
Chan-
ges
during
opera-
tion
Default
setting
Setting
range
DescriptionNamePara
meter
No.
Page
Flux
vector
Open
loop
vector
V/f
with
PG
V/f
control
Chan-
ges
during
opera-
tion
Default
setting
Setting
range
Description
Display
name
C1-11
Accelera-
tion/decel-
eration
switching
frequency
Sets the frequency for automat
-
ic acceleration/deceleration
switching.
Below set frequency: Accel/de
-
cel time 4, above set frequency:
Accel/decel time 1
Note:
The multi function input
0.0 to
400.0
0.0 NO A A A A 5-13
Acc/Dec
SW Freq
Note:
The multi-function input
“multi-accel/decel time 1”
or “multi-accel/decel time
2” take priority
.
Note
The setting range for acceleration/deceleration times will dif
fer according to the setting for C1-10
(the
unit for acceleration/deceleration time.) When C1-10 is set to 0, the setting range for
accel
-
eration/deceleration times becomes 0.00 to 600.00 seconds.
H S-curve Acceleration/Deceleration: C2
Para
Control
mode
Page
meter
No.
Display
name
range setting ges
during
opera-
tion
V/f
control
V/f
with
PG
Open
loop
vector
Flux
vector
C2-01
S-curve
characteris-
tic time at
accelera-
tion start.
Note:
When the S-curve char
-
acteristic time is set the
All sections of the S-curve
characteristic time are set in
seconds units.
0.00
to
2.50
0.20 NO A A A A 6-58
SCrv Acc
@ Start
ac
e
accel/decel times will in
-
crease by only half of
C2-02
S-curve
characteris-
tic time at
accelera-
tion end.
the S-curve characteris-
tic times at start and
end.
Output frequency
0.00
to
2.50
0.20 NO A A A A 6-58
SCrv Acc
@ End
C2-03
S-curve
characteris-
tic time at
decelera-
tion start.
Time
0.00
to
2.50
0.20 NO A A A A 6-58
SCrv Dec
@ Start
C2-04
S-curve
characteris-
tic time at
decelera-
tion end.
0.00
to
2.50
0.00 NO A A A A 6-58
SCrv Dec
@ End
Parameter Lists Chapter
7