EasyManua.ls Logo

Omron SYSDRIVE 3G3FV

Omron SYSDRIVE 3G3FV
400 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
7-22
H Reference Limits: d2
Para
meter
Name
Description Setting
range
Default
setting
Chan-
ges
Control
mode
Page
meter
No.
Display
name
range setting ges
during
opera-
tion
V/f
control
V/f
with
PG
Open
loop
vector
Flux
vector
d2-01
Reference
frequency
upper limit
Sets the output frequency upper
limit as a percentage of the
maximum frequency
.
0.0 to
110.0
100.0 NO B B B B 6-64
Ref Upper
Limit
qy
d2-02
Reference
frequency
lower limit
Sets the output frequency lower
limit as a percentage of the
maximum frequency
.
0.0 to
109.0
0.0 NO B B B B 6-64
Ref Lower
Limit
qy
H Jump Frequencies: d3
Para
meter
Name
Description Setting
range
Default
setting
Chan-
ges
Control
mode
Page
meter
No.
Display
name
range setting ges
during
opera-
tion
V/f
control
V/f
with
PG
Open
loop
vector
Flux
vector
d3-01
Jump
frequency 1
Sets the center value of the
jump frequency in Hz.
0.0 to
400.0
0.0 NO B B B B 6-64
Jump Freq
1
jqy
Note:
This function is disabled
by setting the jump fre
-
quency to 0 Hz Always
d3-02
Jump
frequency 2
quency to 0 Hz. Always
ensure that the following
applies:
0.0 NO B B B B 6-64
Jump Freq
2
a lies:
d3-01
+
d3-02
+
d3-03
Operation in the jump fre
-
quency range is
p
rohib
d3-03
Jump
frequency 3
quency range is prohib
-
ited but during accelera
-
tion and deceleration,
0.0 NO B B B B 6-64
Jump Freq
3
tion
and
deceleration
,
speed changes smoothly
without jump.
d3-04
Jump
frequency
width
Sets the jump frequency
bandwidth in Hz.
Note:
The jump frequency will
0.0 to
20.0
1.0 NO B B B B 6-64
Jump
Bandwidth
Note:
The
jum
frequency
will
be the jump frequency
±
d3-04.
Parameter Lists Chapter
7

Table of Contents